A reading that held still.
At about seven in the evening of Saturday 10 December 2005, unleaded petrol began to flow through a pipeline into Tank 912 at the Buncefield oil storage depot near Hemel Hempstead. The tank belonged to Hertfordshire Oil Storage Ltd and could hold 6 million liters. It stood inside a bund, a wall or embankment meant to contain fuel lost from a tank. The petrol arrived at about 550 cubic meters an hour. In the depot's control room, the supervisors followed the level on the display of an automatic tank gauge. The gauge carried three high-level alarms, and the supervisors relied on those alarms to control the filling.
The tank also had an independent high-level switch, meant to operate at a level above the highest of the three alarms. Once the petrol reached that level, the switch was intended to sound a final alarm and to close the valves on the pipelines bringing fuel in, with no one needing to act.
Around midnight the depot closed to road tankers, and a stock check finished at about half past one with nothing abnormal reported. At about three in the morning the gauge's reading stopped changing. The display went on showing the tank about two-thirds full while petrol kept flowing in. With the reading held still, none of the three alarms could sound, and nothing told the control room supervisor that the level was climbing toward the top of the tank. The switch above them did not act either. It had been fitted in July 2004 without the padlock meant to hold its test lever in the operating position. After the switch's periodic tests the lever had been left in the position that disabled the switch, or free to fall into it.
Some time before 05:40 the level passed the tank's capacity, and petrol began to spill from vents in its roof. A deflector plate at the top turned most of the petrol onto the tank wall, and the petrol fell down the side and through the air, forming a rich mixture of fuel and air that collected in the bund. Security cameras first showed a low mist there at about 05:38. By about 05:46 the mist had become a cloud some 2 meters deep, flowing out of the bund in every direction.
Shortly before six, the flow into the tank rose to close to 900 cubic meters an hour. The supervisors did not know of the change. The pipeline was controlled from elsewhere, and they had no access to its flow rate. Tanker drivers waiting to fill their vehicles in the depot and members of the public outside it noticed the cloud and alerted employees on site. The cloud spread until it was about 360 meters across, part of it beyond the depot.
At 06:01 the fire alarm button was pressed, and by then more than 250,000 liters of petrol had left the tank. The button sounded the alarm and started the firewater pump, and the cloud exploded almost immediately. A spark from the pump as it started probably ignited the cloud, in the judgment of the regulators who later investigated the explosion. The fire that followed engulfed more than 20 fuel tanks across the depot and lasted five days. No one was killed, and more than 40 people were injured.
Tank 912 had two protections against overfilling, and they failed in different ways. The gauge failed in service, and its three alarms failed with it, because all three depended on the one reading it gave. The switch had been built to be independent of the gauge, but it could not act either, and nothing about the switch had shown that it could not. What the night does not show is what would have made those failures harmless: how a protection must be built so that a failed part leaves the tank safe or makes itself known, and how rarely the protection may fail before the risk it leaves is too high to accept.
Let's Talk