Barriers in series.
+ The questionWhen do separate barriers multiply, and what makes a barrier count as one?
Three barriers on one tank
Tank 912 at Buncefield had three barriers against an overfill and what follows it. The first was the automatic gauge with its three alarms, the second the independent high-level switch set above them, and the third the bund, the wall around the tank meant to hold fuel lost from it. On the night the opening describes, each failed in its own way. The gauge stuck, so the alarms set on its reading never sounded. The switch could not act, because after its periodic tests its lever had been left unsecured (Chapter 11). The petrol that spilled from the roof vents fell into the bund, and the vapor from that petrol flowed out of the bund in all directions.
Three barriers in a row look like three chances to stop one event. If each failed on one occasion in 10, all three would fail together on one occasion in 1,000. Buncefield shows the two conditions on which that multiplication rests. The first is that the chances multiply only when the barriers fail for separate reasons, and the alarms did not, because all three read the one gauge. The second is that a barrier counts only against a consequence it acts on, and the bund, built to hold liquid, could do nothing to the cloud of vapor.
Layers from the design outward
A protection layer, or barrier, is anything that can stop a developing event before it becomes harm: a feature of the design, a control system, an alarm with someone to answer it, an automatic trip, a wall, an emergency plan. Layers are drawn as rings around the process, in the order in which an event meets them. The innermost ring is the process design, which sets how much material there is and under what conditions it is held. Next comes the basic control system of Chapter 4, which keeps the process at its set points, and then the alarms and the operator who answers them. The automatic safety function comes after them and takes the process to its safe state without waiting for anyone. Beyond it are the relief devices, which open on pressure alone.
Those rings prevent the event. The rings outside them act once the event has happened and limit what it does: containment such as a bund holds what has been spilled, fire and gas systems detect and fight what escapes, and emergency response protects first the plant and then the community around it. IEC 61511, the process sector's standard for safety instrumented systems, draws the same split, with prevention inside mitigation. Buncefield's gauge and its alarms sat in the rings of control and alarms, the switch in the ring of automatic safety functions, and the bund in the first ring of mitigation.
The incubator of Chapter 4 has fewer rings, in the same order. Its controller sits in the ring of basic control, and the alarm at the cot side, with the nurse who answers it, sits in the ring of alarms. The protective channel with its cutout sits in the ring of automatic safety functions. The cutout is the incubator's counterpart of Buncefield's switch, and the alarm at the cot side is the counterpart of the alarms on the gauge.
Why independent layers multiply
A layer is called on only when an event reaches it, and each such call is a demand. On each demand the layer either acts or fails. The chance that it fails on a demand is its probability of failure on demand, or PFD: a layer with a PFD of 1 in 10 lets one demand in 10 pass. Harm needs the initiating event of Chapter 5 and then the failure of every layer in its path. If the first layer lets a tenth of the events through, and the second fails on one demand in 10 whatever the first has done, a tenth of that tenth passes the second as well: one event in 100. A third such layer leaves one in 1,000.
The frequency of a consequence is therefore the frequency of its initiating event multiplied by the PFD of every layer in the way. The product explains why several modest layers can protect as well as one outstanding layer. Three layers that each fail on one demand in 10 cut the frequency 1,000-fold, as much as a single layer that fails on one demand in 1,000. This chapter takes each layer's PFD as given, and Chapter 11 shows how an instrumented layer's PFD follows from its failure rate and its test interval.
The product rests on the condition hidden in the words "whatever the first has done": the chance that the second layer fails must be the same whether or not the first has failed. A layer is independent, in this sense, when nothing that causes the initiating event and nothing that defeats another layer can also defeat it. Where one cause can fail two layers together, the second layer's chance of failing is no longer 1 in 10 once the first has failed: it is close to certain. The factor that an analysis allows a layer is called its credit. With a shared cause, the product credits the second layer with a protection that is not there. The first question to ask of any layer is therefore what it shares with the event and with the other layers.
What makes a barrier count
An independent protection layer is a device, system or action that can stop a scenario before it reaches its consequence, without being affected by the initiating event or by any other protection layer in the same scenario, as the Center for Chemical Process Safety defines it. A scenario, in this sense, is one initiating event and the chain that leads from it to one consequence. The definition's first clause asks that the layer can do the job. To do it, a layer that responds to the event, such as a trip or an alarm, needs the shape of the safety function of Chapter 4: something that detects, something that decides and something that acts, within the time the process allows. A passive layer such as the bund has none of these parts and does its job by holding the fuel lost from the tank. An alarm becomes a layer only with someone who hears it, knows what to do and can stop the fill in time (Chapter 9). The second clause is the independence that the product needs. One safety consultancy's training course applies the definition through four criteria: independence and three more.
A layer must be specific: designed to act against the scenario in question, and so against its consequence. The bund shows why the criterion stands apart from the others. Against one consequence of an overfill, liquid spreading across the site and into the ground, a sound bund is a strong barrier. Buncefield's bunds were not sound. The Competent Authority, the regulators who investigated the explosion, found in 2011 that in the fire the bunds failed badly at their joints and where pipes passed through their walls. Against another consequence, a cloud of vapor drifting off the site, a bund is no barrier at all, because it holds a liquid and does nothing to what evaporates from it. In an analysis of the explosion a bund therefore earns no credit, however well it is built, and in an analysis of the pollution it may earn a great deal.
A layer must also be dependable, which means that it cuts the frequency at least tenfold, and auditable, which means that its performance can be checked by review, testing and records. A PFD that nobody tests cannot enter the product, because nothing shows that the layer fails as rarely as the number says.
LOPA multiplies the layers of one scenario
Layer of protection analysis, or LOPA, applies the product to one scenario at a time. The scenario starts from one initiating event and its frequency a year. Some initiating events lead to the consequence only if a condition holds at the time, such as a fill large enough to overflow the tank, and the probability of that enabling condition multiplies the frequency. Each layer that meets the criteria multiplies the frequency by its PFD, and a layer that fails them earns a factor of 1. Last come the conditional modifiers, the probabilities on which the harm depends but which no layer controls, such as whether escaping vapor ignites and whether anyone is near. The result is the frequency of the consequence, which the analysis compares with the frequency judged tolerable for that consequence (Chapter 6).
The method is deliberately coarse. Its values are rounded to tenfold steps, and generic tables supply them where a plant has no data of its own. Two such tables, one in a chemical engineering textbook and the other in the same consultancy's training course, give the same value wherever both list an item. A control loop fails, as an initiating event, about once in 10 years. An operator answering an alarm has a PFD of 1 in 10, a relief valve 1 in 100 and an instrumented safety function 1 in 10, the value the course gives for the lowest integrity level. The textbook's table also gives a bund 1 in 100.
The scenario is a tank of petrol filled from a pipeline: the level gauge fails, stops following the level, and the fill runs on. The tables give such a failure of a control loop about once in 10 years, 0.1 a year. Two layers stand in the way. An operator answering a high-level alarm on its own sensor has a PFD of 0.1. An independent trip that closes the inlet valve is credited at 0.1, the value given above for an instrumented safety function of the lowest integrity level (Chapter 8). The tank overfills at 0.1 × 0.1 × 0.1 = 0.001 a year, about once in 1,000 years. If the alarm takes its level from the failed gauge, it cannot act when the gauge fails, so its factor is 1. The overfill then comes at 0.1 × 1 × 0.1 = 0.01 a year, about once in 100 years. One shared sensor has made the overfill 10 times as frequent. A bund at 0.01 cuts the frequency of liquid escaping beyond it to 0.001 × 0.01 = 0.00001 a year, or 1 in 100,000. Every overfill of petrol is taken to form a cloud, as Buncefield's did, so the frequency of a vapor cloud stays at 0.001 a year. These are frequencies of the overfill and its cloud, not of harm. The conditional modifiers, ignition and someone present, are applied before any comparison with a tolerable frequency.
PSLG's 2009 guidance for fuel storage sites applies LOPA in this form to the overfilling of a tank, and sums the frequency over every initiating event that can overfill it (Chapter 22). In any LOPA, a frequency of the consequence above the tolerable frequency leaves a shortfall: the factor by which the frequency must still be reduced. A further layer is added to supply that factor, and Chapter 8 turns the shortfall into the integrity level the new layer must reach.
A shared cause breaks the product
The solved example's second case is what happened at Buncefield. The supervisors followed the fill on the gauge's reading and relied on its alarms to tell them when to act. The one gauge that stuck therefore both let the fill run on and silenced the three alarms set on its reading. Because each alarm read the same frozen number, the three were at most one layer, and against a failure of the gauge itself they were none. The switch sensed the level through the tank's floating deck, not through the gauge. It was therefore independent of the gauge, and its failure had a cause of its own.
Shared causes can also lie outside the equipment. The Competent Authority found failures of management behind both instruments. The site had no effective process for logging the gauge's faults and no maintenance regime that could reliably respond to them (Chapter 20). The site operator did not exercise enough oversight of how the switch was ordered, installed and tested (Chapter 17). The site's management also failed to scrutinize the combined unreliability of the gauge and the inoperable switch. Generic PFDs assume that each layer is tested and maintained as its credit requires. A failure in that care is a cause that can degrade every layer at once, and two instruments that share no wire can still share that cause.
Chambers and colleagues at the Health and Safety Laboratory found the same weakness in practice. In a 2009 review commissioned by HSE, they examined the overfill LOPAs of seven companies, with the input values and methods of each. Among the faults they found were causes shared between initiating events and layers: a control system, a tank gauge or an operator on which both the event and a credited layer depended.
The process sector's standard limits the credit that a basic control system can take in one scenario. Under IEC 61511-1, where a basic control system that is not built to the standard causes the demand, no more than one of its layers may be claimed in the same scenario. A claim of more than a tenfold reduction for a layer of the basic control system requires the system to be managed to the standard.
The incubator meets the same question at its sensors. The alarm at the cot side shows what the controller sees (Chapter 4). A thermistor that drifts low, as in Chapter 1, therefore makes the controller heat harder and keeps the alarm silent. The drift is then at once the initiating event and the failure of the alarm layer, as the stuck gauge was. The protective channel escapes that cause because it has its own sensor. It does not escape a cause that reaches both channels, such as their shared power supply, their enclosure or the air stream both sensors sit in. Chapter 14 shows how far such causes raise the chance that both channels fail together.
A LOPA worksheet lists each layer by name. Two trips through one logic solver, or two checks by one person on one shift, each take a row of their own and fail as one. The parts a layer may need are its sensor, its logic, its final element, its person and its power. A row's credit holds only if none of those parts is involved in the initiating event or appears in another credited row.
For each scenario, list the parts each credited layer needs and strike the credit of any layer that shares one of them with the initiating event or with another credited layer. Credit a layer only against the consequence it acts on, and only at a PFD that its tests and records can show. For a device such as the incubator, give the alarm at the cot side its own sensor, or credit it with nothing against a failure of the control sensor. Record each credited layer, its PFD and the test that checks it in the safety requirements specification (Chapter 17).
- Protection layers stand in the order an event meets them, from the process design through control, alarms and automatic safety functions to containment and emergency response. The inner rings prevent the event, and the outer rings mitigate it.
- Independent layers multiply: the frequency of a consequence is the initiating event's frequency times each layer's probability of failure on demand, so three layers at 1 in 10 cut it 1,000-fold.
- A barrier counts only if it acts on the consequence in question, cannot be defeated by the initiating event or another layer, and can be shown by test and records to perform as credited. Buncefield's bund, built to hold liquid, could do nothing to the cloud of vapor.
- A shared cause breaks the product: at Buncefield one stuck gauge both let the fill run on and silenced the three alarms set on its reading, so against a failure of the gauge they were no layer at all.