+ Part VII · The field in 2026

Who builds and who assesses.

The earlier chapters met products one at a time, each to show a principle. This part takes the supply of a safety function as a whole, layer by layer, from the bodies that certify products to the chips inside a controller and the devices in the plant. Its one chapter describes the products of each layer, the form their claims take and the conditions those claims pass to whoever builds the products in, India included, and ranks none of them. It names the makers of safety controllers, safety chips and field devices, and the bodies that assess them, as of November 2026, because companies change while their products stay in service. On 29 June 2026, for example, Honeywell completed the spin-off of its aerospace business, and the company that remains, renamed Honeywell Technologies, describes itself as "a global, pure-play automation company".

27 — The field in 2026

Makers and assessors, India included.

+ The questionWho makes safety controllers, safety silicon and field devices, and who certifies them?

Five bodies stand behind the certificates

A safety controller is sold with a certificate, and five assessment bodies are named as the assessors of the products in this chapter: exida, TÜV Rheinland, TÜV SÜD, TÜV NORD and Risknowlogy. Chapter 21 read what such a certificate states, and Chapter 19 what stands behind the body that issues it. Both readings apply in every layer, from the controller to its chip, its operating system, its compiler and the valve it drives. What changes from layer to layer is the thing assessed and the conditions its certificate sets.

61 — Who works in each layer of a safety function, as of November 2026
ACCREDITATION ANAB (US) DAkkS (Germany) NABCB (India) IN ACCREDITS ASSESSMENT AND CERTIFICATION CSA Group exida IN Risknowlogy TÜV NORD IN TÜV Rheinland IN TÜV SÜD IN UL Solutions CERTIFICATE SAFETY CONTROLLERS Emerson · DeltaV, integrated SIS HIMA · HIMax Pilz · PSS 4000 (machines) Yokogawa · ProSafe-RS Sensor Logic solver Final element SILICON AND CORES Arm · Cortex-R52+ (licensed design) Infineon · AURIX TC3x, TC4x OPERATING SYSTEMS HighTec · PXROS-HR WITTENSTEIN · SAFERTOS COMPILERS AND VERIFICATION TOOLS Arm · Compiler 6 HighTec · TriCore compiler TASKING · LDRA tools IN FIELD DEVICES: SENSORS Endress+Hauser · Liquiphant IN KROHNE · OPTIWAVE Pyro Electric · resistance thermometers, thermocouples IN Siemens · SITRANS P VEGA · VEGAPULS 6X FIELD DEVICES: VALVE CONTROLLERS Fisher (Emerson) · DVC6200 SIS Flowserve · Logix 3800e CERTIFICATE CERTIFICATE A certificate names its assessor, its holder and its conditions (Chapter 21) ENGINEERING SERVICES AND PEOPLE Bureau Veritas IN DEKRA IN exida (integrators, engineers) IN SGS IN TÜV NORD (TUV India) IN UL Solutions (engineers) IN works in India Companies and products as each maker or assessor states them, 18 November 2026. Schematic.
Focal detail
Plate 61 — Every layer of a safety function has its own makers, and each part's statement of its integrity is the maker's own or an assessor's certificate, whose issuer an accreditation body in turn recognizes. The names are those of this chapter, in alphabetical order within each layer; the tags mark work in India.

The assessors sell more than one kind of assessment, and each accreditation names the kind of work it recognizes (Chapter 19). ANAB, a US accreditation body, accredits Exida Certification, exida's certifying company, as a testing laboratory under ISO/IEC 17025:2017. That accreditation covers functional safety tests to IEC 61508, IEC 61511, ISO 26262 and five other standards, and it runs from 24 December 2025 to 24 December 2027. A body that certifies products is accredited under ISO/IEC 17065 instead. ANAB also lists Exida Certification among the product certification bodies it accredits, and TÜV Rheinland states that its own accreditation comes from DAkkS, Germany's national accreditation body. A test report and a product certificate can carry the same company's name, and each rests on its own accreditation.

Bodies of the same kind also certify people and organizations: exida certifies engineers as Certified Functional Safety Experts or Professionals, and UL Solutions runs two personnel schemes of its own. CSA Group certifies a company's functional safety management, and exida's IEC 61511 Certified Integrator Program certifies that an integrator's project execution practices comply with IEC 61511. Such a certificate covers the engineer or the practices, and no product that either one uses.

A certificate also names its holder as of the day it was issued. In 2010 exida certified Endress+Hauser's Liquicap M for Endress+Hauser GmbH + Co KG, and in 2023 TÜV Rheinland certified the maker's Liquiphant level monitors for Endress+Hauser SE + Co. KG. The one maker thus appears under two assessors and two legal names. Larger changes follow splits and sales. Besides Honeywell's renaming at the head of this part, OMRON's business in relays, switches, connectors and sensors became a separate company, renamed Aratas Corporation, on 1 July 2026. Aratas is the publisher of Chapter 10's relay figures. ABB announced on 8 October 2025 that it would sell its robotics division to SoftBank Group. A buyer therefore matches the holder on each certificate to the company that sells the part today.

Safety controllers state how they reach SIL 3

In a process plant the logic solver of Chapter 4 is a programmable safety controller, of the kind whose generations Chapter 12 traced. Yokogawa describes its ProSafe-RS as "SIL3 certified in a single module configuration" by TÜV. Each of its processor, input and output modules has a dual architecture. Further cards add redundancy to any function while the system keeps SIL 3, so the redundancy is not what earns its rating. HIMA's HIMax appears in exida's equipment list as a logic solver with "diagnostic-based SIL 3 safety integrity", and the list names TÜV Rheinland as its assessor. That rating rests on the controller's checks on itself (Chapter 12).

Yokogawa and Emerson integrate their safety controllers with their control systems, and integration is where a common cause between control and protection has to be examined (Chapter 14). The ProSafe-RS runs on the same network as Yokogawa's CENTUM VP control system, with no gateway between them. Emerson released DeltaV 16.LTS in January 2026, and a trade journal reported that the release brings software-defined automation to the control system and its "integrated safety instrumented system". The certification named with the release is ISA's System Security Assurance at Level 1, and it concerns protection against attack rather than against the system's own failures.

Machines have safety controllers of their own (Chapter 23). TÜV SÜD Product Service certifies Pilz's PSS 4000 and PSSu systems up to SIL 3 under IEC 61508 and up to performance level e in Category 4 under ISO 13849-1, and also against IEC 62061 and IEC 61511. The certificate is valid until 5 November 2028. One certificate thus grades the same controller in the terms of machines and of process plants alike.

Chips, operating systems and tools carry conditions forward

Inside a safety controller sit a processor, an operating system and code that a compiler built. Each can come from a different company and be assessed before the system that will use it exists. Arm licenses processor designs, and the chip makers that license them build and sell the silicon. The Cortex-R52+ is a real-time core for functional safety applications, and Arm lists a certificate for it to ISO 26262 and IEC 61508, with others for a software test library that runs on the core. Arm Compiler 6 is listed with TÜV SÜD in class T3 of IEC 61508-3, the class that Chapter 15 gives a compiler.

Infineon's AURIX TC3x and TC4x are families of 32-bit microcontrollers. HighTec describes itself as a preferred design house of Infineon. For the TC4x it sells a compiler that it calls "Compliant with ISO 26262 ASIL D", with a qualification kit certified by TÜV up to ASIL D, and an operating system, PXROS-HR, which it states is certified at ASIL D and SIL 3. WITTENSTEIN high integrity systems states that its SAFERTOS is "independently certified by TÜV SÜD" at SIL 3 under IEC 61508-3. Under "Compliant to" the company lists DO-178C, FDA 510(k) and EN 50716. The two words differ in who stands behind them: "certified" names an assessor, and "compliant" is the maker's own statement. As for the 510(k), FDA clears one for a device, not for the operating system inside it.

TASKING, a maker of development tools for safety-critical software, announced in February 2025 that it had acquired LDRA. LDRA's tools trace requirements, analyze code and verify units and systems, and its teams are in the United States, India and Germany. An element assessed before its system exists holds its certificate on the conditions of its safety manual (Chapter 21). Whoever builds a chip, an operating system and a compiled program into one controller therefore takes on the conditions of all three.

Field devices state their levels in different words

Sensors and final elements come from instrument makers, and their statements of integrity differ in wording and in whose statement each one is: the maker's or an assessor's.

DeviceStatementWhose statement
Endress+Hauser Liquiphant FTL51B, FTL62, FTL63 and FTL64 level monitorsSIL 2 at HFT 0; systematic capability SIL 3, usable at HFT 1TÜV Rheinland's certificate, 2023
VEGA VEGAPULS 6X radar level sensor"suitable for use up to SIL2"; SIL 3 with redundancythe maker's; exida's list names TÜV NORD as its assessor
KROHNE OPTIWAVE radar level transmittersfor a "SIL 2/3 safety function"; SIL 3 in a 1oo2 architecturethe maker's, 2021
Siemens SITRANS P310, P DS III and P410 pressure transmittersSIL 2 in 1oo1; up to SIL 3 in a redundant 1oo2Risknowlogy's proven-in-use report, 2015
Fisher FIELDVUE DVC6200 SIS digital valve controller"meets the systematic integrity requirements of SIL 3"the maker's; exida's list gives SIL 3 for the DVC6200
Flowserve Logix 3800e digital positioner"SIL 3 capable"the maker's

The assessors reached their statements by two routes. TÜV Rheinland certified the Liquiphant to IEC 61508. Risknowlogy based its statement for the Siemens transmitters on failure data from devices in use, the proven-in-use route of Chapter 15, in a 2015 report whose client was Siemens. Three of the six statements give SIL 2 for one device and SIL 3 for a redundant pair, whose fault tolerance Chapter 13 explains. The Liquiphant's certificate allows its systematic capability of SIL 3 to be used in such a pair. Certificates of other kinds, such as Flowserve's approvals for hazardous areas and VEGA's certificate to IEC 62443-4-2 for cybersecurity, concern protection against explosion and attack rather than the device's own failures.

A final element is an assembly of valve, actuator and controller, and the controller can test the rest while the plant runs. In a partial stroke test it moves the valve through only part of its travel. The DVC6200 SIS moves the valve along a short ramp that the user sets, enough to detect a stuck valve without disturbing the process, and it aborts the test if its output pressure passes a threshold. Full stroke tests are run offline. Because a partial stroke test exercises only part of the valve's travel, in the terms of Chapter 11 it reveals only some of the failures that a full stroke would.

Solved example: the highest level a function built from three makers' parts may claim

Here a function's sensor is one Liquiphant level monitor, its logic solver a HIMax and its final element a valve driven by a DVC6200 SIS. The monitor's certificate gives SIL 2 with no fault tolerance and a systematic capability of SIL 3. The controller is listed at SIL 3, and the valve controller's maker states SIL 3 for its systematic integrity. A function may claim no more than the lowest ceiling among its elements (Chapter 21), so with one monitor it stops at SIL 2, however low its average. Two monitors arranged so that either can act give a fault tolerance of one. At that fault tolerance the certificate states that the systematic capability of SIL 3 can be used. Route 1H of Chapter 13 then lifts the hardware ceiling to SIL 3 where the safe failure fraction allows it, and route 2H does so where the field reliability data allow it, so the lowest ceiling rises to SIL 3. The valve controller's statement does not cover the valve and its actuator. The function reaches SIL 3 only if those two carry ceilings of SIL 3 as well, and if the average computed from every part's rates lies in the SIL 3 band. One monitor gives SIL 2 at most, and two give SIL 3 at most, on those two conditions.

62 — The lowest ceiling among three makers' parts sets the function's ceiling
One Liquiphant monitor SIL 1 SIL 2 SIL 3 SIL 4 Sensor Liquiphant, HFT 0 TÜV Rheinland certificate Logic solver HIMax · listed by exida, assessed by TÜV Rheinland Final element DVC6200 SIS: SIL 3, systematic · maker's statement; exida's list Valve and actuator: ceilings of their own Function: SIL 2 at most Two Liquiphant monitors, either can act (HFT 1) SIL 1 SIL 2 SIL 3 SIL 4 Sensor pair, HFT 1: systematic capability SIL 3 usable Logic solver as above Final element as above Valve and actuator: ceilings of their own Function: SIL 3 at most, if the valve, its actuator and the average reach it the lowest ceiling Levels as stated: TÜV Rheinland certificate for Liquiphant FTL51B, FTL62, FTL63, FTL64 (2023); exida's equipment list (accessed 18 Nov 2026); Fisher product bulletin 62.1 (2023). Rule: Chapter 21. Schematic.
Focal detail
Plate 62 — The function takes the lowest of its parts' ceilings. One monitor holds it to SIL 2; a pair that tolerates one fault lifts the sensor's ceiling to SIL 3 where the reliability data or the safe failure fraction allow it, and the function reaches SIL 3 only if the valve and actuator carry that ceiling too and the average lies in the SIL 3 band.

Engineering firms and India

Between the makers and the plant stand the firms that analyze hazards, verify functions and integrate systems, and the testing and certification companies sell these services too. On its page for India, SGS lists services under the second edition of IEC 61511: training, workshops on probabilistic calculations, gap analysis, the verification of a safety function's design with its calculations, and the certification of engineering processes and applications. Bureau Veritas's Indian companies list SIL assessments, FMEA and hazard studies. DEKRA carries out Chilworth Technology's process safety work in India through DEKRA (India), in Delhi, Mumbai and Hyderabad.

Several assessors offer their own services in India. TÜV SÜD South Asia runs a four-day course on IEC 61508 that leads to a personnel certificate, which it calls "Globally accepted" and "with non-expiry". TÜV Rheinland's page for India offers functional safety assessments of components that lead to its test mark. TUV India, part of the TÜV NORD Group, lists functional safety among its product certification services, and it has branch offices in cities that include Bangalore and Pune. India is also among the service centers that exida lists. NABCB, the National Accreditation Board for Certification Bodies, accredits bodies that certify products in India under ISO/IEC 17065, and it is a signatory of the International Accreditation Forum's arrangements for mutual recognition.

The makers in India named here hold assurance of different kinds. Pyro Electric, of Goa, achieved certification to IEC 61508 for its series 100 to 900 of resistance thermometers and thermocouples through the proven-in-use route. Its assessor, Risknowlogy, announced the certification on 28 December 2025. Sapcon Instruments, an Indian maker of level sensors, lists approvals from PESO for its fork level sensors, and PESO administers India's petroleum and explosives laws (Chapter 30). Endress+Hauser's Indian company makes flow, level, pressure, analysis and temperature instruments at Chhatrapati Sambhajinagar, formerly Aurangabad.

Read each layer's claim for who stands behind it

For every part of a safety function, record its maker, whose statement its integrity level is, and the document that states it, with its date and revision (Chapter 21). Treat a statement that names no assessor as the maker's own claim, to be checked against an assessor's certificate, and check that the assessor's accreditation covers the kind of work the certificate reports. Match the holder named on each certificate to the company that sells the part today. For chips, operating systems and tools, carry the conditions of their safety manuals into the safety requirements specification (Chapter 17), since they become conditions on the function.

+ What this chapter established
  • Five assessment bodies are named as this chapter's assessors, and an accreditation names the kind of work it recognizes: testing under ISO/IEC 17025 or product certification under ISO/IEC 17065. Personnel and integrator certificates cover people and practices, not products.
  • Yokogawa's and HIMA's safety controllers reach SIL 3 by a dual architecture in one module or by diagnostics. When the chips, operating systems and tools inside a controller are assessed before their system exists, whoever builds them in takes on the conditions of their safety manuals.
  • Field devices state their levels in different words and on the maker's or an assessor's authority, and a function built from three makers' parts may claim no more than the lowest of their ceilings, which in the solved example is SIL 2 with one Liquiphant monitor.
  • In India the testing and certification companies and the assessors named here offer training, personnel certificates, assessments and engineering services. Risknowlogy, Pyro Electric's assessor, announced in December 2025 that the Goa maker had achieved an IEC 61508 certification through the proven-in-use route.
Created with Claude (Anthropic).
Educational reference material, not engineering, regulatory or clinical advice. Product and company names referenced are the property of their respective owners.