21 — Reading a safety claim

What a certificate promises.

+ The questionWhat does a SIL certificate or a safety manual promise, and what is left to the buyer?

Two statements about one switch

A certificate for a level switch prints "SIL 3 Capable" and "SIL 2 @ HFT=0", which are statements about the switch and not about any plant. The switch is the Rosemount 2130, the vibrating-fork switch whose proof test Chapter 20 followed, and Emerson makes it under its Rosemount brand. The certificate is the assessor's: exida, a certification and consulting company, issued it to the maker and declares in it that the switch complies with IEC 61508:2010. The revision used here is Revision 3.4, dated 14 July 2022. Certification to IEC 61508 is voluntary. Chapter 19 sets out who assesses a product and under what regime.

The first statement concerns systematic failures, the faults of specification, design and making that Chapter 3 set apart from random ones. On the certificate "SIL 3 Capable" stands beside "SC 3", the systematic capability of Chapter 15, and the two name one ceiling. In such a statement capable names that systematic ceiling: the highest integrity level that the element's systematic capability allows a safety function to claim, judged from the element alone. The element's hardware sets a second ceiling, which the next statement gives. A function built from the element does not reach either level by including it, because the function's level depends on all its parts, on how they are arranged and on how often they are tested.

The second statement concerns random hardware failures, and its ceiling depends on how the switches are arranged. "SIL 2 @ HFT=0, SIL 3 @ HFT=1" means that one switch on its own may serve a function of up to SIL 2, with a hardware fault tolerance of zero, that of a single channel in Chapter 13. Two switches arranged so that either can act have a tolerance of one, and together they may serve a function of up to SIL 3. A switch whose systematic ceiling is SIL 3 is thus held to SIL 2 by its hardware whenever it stands alone.

The certificate classes the switch as a Type B element, which its safety manual describes as a "complex device using controllers or programmable logic". The certificate also names Route 2H, the route of Chapter 13 that rests on reliability data from field feedback. The assessor's FMEDA, an analysis of the switch that the maker commissioned, predicts the switch's rates from the assessor's own database of component failure data, and the FMEDA report says that the switch meets the route's condition component by component. That database is built on field data from the process industry and on published prediction methods. The assessor states that IEC 61508 gives no detailed criteria for the route, and it applies criteria of its own: every component needs 10 million operating hours in the field, or more than 10 years of known common use in at least 10 units. The certificate's rates are therefore predictions for the switch, built up from data on its parts.

The certificate holds on its stated conditions

Each statement is conditional, and the certificate lists the conditions. The switch is to be designed into a safety instrumented function as its safety manual requires, and a function designed with it is not to be used at an integrity level higher than the certificate states. Each element is to be checked against the minimum hardware fault tolerance, and the PFDavg and the architectural constraints "must be verified for each application". Two documents are mandatory beside the certificate: the maker's safety manual, at Revision AJ or later, and the assessor's report on the switch. The certificate thus states what the switch can be used for, as Chapter 8 put it, and leaves the proof that a function meets its own target to whoever builds the function.

The certificate covers named versions of the switch only. It gives rates for five output types, from a relay to an output of 8 or 16 mA, each in two modes: dry, with the output on while the fork is dry, and wet, with the output on while the fork is wet. The safety manual narrows the certified versions further. Switches ordered with option code QT carry the third-party certificate and a yellow tag, while code QS brings the maker's own "prior use FMEDA certificate" instead. The firmware must also be at or above a stated version. A buyer who orders the switch without code QT, or installs older firmware, holds a switch outside the assessor's certificate.

The certificate's figures are bounded in time. Revision 3.4 prints a surveillance audit due on 1 January 2024, and the assessor's FMEDA report records that audit in a version of November 2023. The report's version of March 2024, the one that Chapter 18 followed, prints the same rates as Revision 3.4. The assessor's list of certified equipment now links a later revision of the certificate, Revision 4.0, so a buyer relying on Revision 3.4 asks the assessor which revision is in force and whether its figures have changed.

The rates also carry the FMEDA's assumptions, among them constant rates and one failure at a time, and the report states its scope on human error in two ways. One of its sections leaves out failures caused by errors of operation or by maintenance capability, as specific to each site. Its management summary, by contrast, says that the predictions include site-specific failures due to human events for the site safety index that it specifies. The site safety index is a figure for the site of use, and the report specifies an index of 2, the value printed with its table of rates. At Buncefield a lever left unsecured after the switch's tests disabled the switch, a failure of installation and maintenance at one site (Chapter 11). Failures of that kind are the ones that the first of the report's two statements leaves to each site.

The safety manual carries the rest

IEC 61508-2 asks the maker of a compliant element for a safety manual. The 61508 Association's guide to certificates and safety manuals sets out what the standard's Annex D asks the manual to contain. In the guide's checklist the manual identifies the element and its revision and gives each failure mode with its rate. The manual also gives the diagnostic coverage and safe failure fraction, the diagnostic test interval, the element's fault tolerance, type, systematic capability and route, the service lifetime, the proof-test requirements and the way to report failures. For the 2130 the two documents share the list: the rates stand on the certificate, by output type and mode, and the maker's manual, in its revision of June 2025, carries the conditions, the tests and the service lifetime, which the manual calls the useful life.

Read line by line, the manual first restates the claim in three parts: SIL 2 for random integrity at a fault tolerance of zero, SIL 3 at one, and SIL 3 for systematic capability. The switch's diagnostics run to completion within one hour, the diagnostic test interval of Chapter 12, so a failure that they detect is found within the hour. Chapter 12's rule sets that hour against the process safety time. The switch's useful life is 10 years, set by the worst-case wear-out of its components rather than by wear of the parts in contact with the process. The constant rates of Chapter 10 hold only within that life, so a calculation can use them for no longer. The wear of the fork in a corrosive or abrasive product is the buyer's to judge.

The proof-test procedures, comprehensive and partial, are those that Chapter 20 followed, and so is the requirement to report every failure that the switch's diagnostics or a proof test detects. What the manual adds here is a table of how much each test finds. For every output type and mode the table gives the proof-test coverage of Chapter 11, the share of the dangerous undetected failures that the test reveals, and the rate left over. For the 8/16 mA output set dry, the comprehensive test reveals 93 %, and the partial test, which leaves the fork itself untested, reveals 90 %. Across the table the figures run from 77 % to 98 %. The coverage is the maker's prediction, and the test that the site actually runs decides which figure applies.

The manual leaves the proof-test interval to the user. Proof tests are to come at intervals no longer than those that the user's SIL verification calculation assumes. The rate, the coverage and the useful life are given, and the interval, the number that turns them into a probability of failure on demand, is the buyer's.

44 — The 2130's certificate and safety manual, read line by line
THE LINE AS PRINTED WHAT IT PROMISES LEFT TO THE BUYER CERTIFICATE · ASSESSOR: EXIDA · REVISION 3.4 · 14 JULY 2022 SC 3 (SIL 3 Capable) systematic ceiling: up to SIL 3 the ceilings of every other element SIL 2 @ HFT=0 · SIL 3 @ HFT=1 hardware ceiling: SIL 2 alone, SIL 3 with a second switch, either one acting the arrangement; beta for a pair TYPE B · ROUTE 2H a complex device; a route resting on field data — RATES IN FIT, 8/16 mA OUTPUT, DRY: SD 0 · SU 155 · DD 171 · DU 25 predicted rates for one output and mode the row: output, mode, option code QT, firmware “PFH/PFDavg and Architecture Constraints must be verified for each application” — the function's own figure “Surveillance Audit Due January 1, 2024” a dated document the revision in force SAFETY MANUAL · MAKER: EMERSON · REVISION AM · JUNE 2025 DIAGNOSTICS COMPLETE WITHIN ONE HOUR a detected failure shown within the hour the hour against the process safety time PROOF-TEST COVERAGE, 8/16 mA, DRY = ON: COMPREHENSIVE 93 % · PARTIAL 90 % the share of DU each test reveals the test the site runs USEFUL LIFE 10 YEARS constant rates for 10 years; wear of wetted parts excluded the mission time; wear of the fork PROOF TESTS AT INTERVALS NO LONGER THAN THE SIL VERIFICATION CALCULATION — THE INTERVAL the number the documents leave to the buyer Certificate: exida, Revision 3.4 (2022), the revision used here; the assessor now lists Revision 4.0. Safety manual: Emerson, Revision AM (2025). One row of rates shown: 8/16 mA output, dry = on.
Dangerous failureSafe stateDiagnosticsOperator and alarmFocal detail
Plate 44 — The certificate gives the switch's ceilings, its predicted rates and the conditions of use, and the safety manual its diagnostics, test coverage and useful life. The proof-test interval, the mission time and the function's own figure are left to the buyer's calculation.

The buyer computes the function

The buyer's arithmetic starts by choosing the row that matches the switch as installed. For an overfill duty the fork is dry in normal operation, so the example takes the 8/16 mA output set dry. That output is on while the fork is dry and goes off when the liquid reaches the fork, the de-energized state that Chapter 2 makes the safe one. The row gives no safe detected failures, 155 FIT of safe undetected, 171 FIT of dangerous detected and 25 FIT of dangerous undetected, Chapter 2's four classes as the assessor predicts them. The switch's own diagnostics detect 141 of the 171 FIT. The other 30 FIT drive the output current high or low, and the assessor counts them as detected by the logic solver, so they are detected only where the logic solver acts on such a current.

By Chapter 12's ratios the diagnostic coverage is 171 ÷ 196, about 87 %, with the logic solver's 30 FIT included. The safe failure fraction is (155 + 171) ÷ 351, about 93 %, high partly because of the 155 FIT of safe failures, which trip the plant without a demand, as Chapter 12 warned. Neither ratio sets the switch's ceiling. Under the certificate's Route 2H the least fault tolerance is set by the integrity level, without the safe failure fraction that the other route uses. The 25 FIT of dangerous undetected failures are what the proof test and its interval govern. The example therefore states its interval as an assumption: the comprehensive test once a year.

Solved example: the switch's share of an overfill loop, tested once a year

The buyer assumes that the comprehensive test runs once a year, revealing 93 % of the 25 FIT, and that the mission time equals the manual's useful life of 10 years, or 87,600 hours. A detected failure is assumed repaired within the 8 hours of PSLG's example. The covered share averages 0.93 × 25 × 8,760 ÷ 10⁹ ÷ 2, about 1.02 in 10,000, and the uncovered share 0.07 × 25 × 87,600 ÷ 10⁹ ÷ 2, about 0.77 in 10,000 (Chapter 11). The detected failures add 171 × 8 ÷ 10⁹, about 0.01 in 10,000, so the switch's share is about 1.8 in 10,000. PSLG's loop of Chapter 11 has a transmitter, a logic solver at about 7.1 in 10,000 and a valve at about 0.3 in 10,000. With the switch in the transmitter's place, the loop averages about 9.2 in 10,000, just inside Chapter 8's SIL 3 band. The loop is still a SIL 2 function at most, because its single switch has a fault tolerance of zero and its certificate allows that arrangement no higher than SIL 2. Tested every five years instead, the switch alone averages about 5.9 in 10,000, and with the logic solver's share the loop passes 1 in 1,000 into the SIL 2 band. PSLG's figures for the logic solver and the valve are fictitious, so the loop describes no real tank.

Each figure in the example comes either from the switch's documents or from the buyer. The 25 FIT stand on the certificate and the 93 % in the manual, while the year, the 10-year mission time, the repair time and the rest of the loop are the buyer's. Put in the place of PSLG's transmitter, the switch lowers the loop's average from about 3.8 in 1,000 to about 9.2 in 10,000 and carries about a fifth of the new average. The level that the function may claim stays at SIL 2.

45 — One switch in an overfill loop: the average against the ceiling
1 IN 1,000 SIL 3 BAND SIL 2 BAND SWITCH TESTED YEARLY SWITCH TESTED EVERY 5 YEARS SWITCH, UNCOVERED 0.77 LOGIC SOLVER 7.1 VALVE 0.3 SWITCH, COVERED 1.02 9.2 SWITCH, COVERED 5.1 13.0 WITHOUT THE VALVE AVERAGE IN THE SIL 3 BAND · ONE SWITCH (HFT 0): SIL 2 AT MOST 0 5 10 15 PFDavg, IN 10,000 Switch: 8/16 mA output, dry = on; dangerous undetected 25 FIT; coverage 93 %; mission time 10 years; detected failures about 0.01. Logic solver and valve: PSLG 2009, Appendix 4 Annex 3, fictitious values.
Dangerous failureFocal detail
Plate 45 — With a yearly comprehensive test the switch adds about 1.8 in 10,000 to PSLG's loop, and the loop's average of about 9.2 in 10,000 lies in the SIL 3 band, yet a single switch holds the function to SIL 2 at most. Tested every five years, the switch and the logic solver alone pass 1 in 1,000.
A capable switch caps the function it joins

"SIL 3 Capable" is easily read as a switch that makes a SIL 3 function. The phrase names the switch's systematic ceiling, and the switch's hardware ceiling standing alone is SIL 2. A function may claim no more than the lowest ceiling among its elements and no more than the band its average reaches. In the example the average lies in the SIL 3 band, but the single switch's hardware ceiling holds the function at SIL 2. A second switch arranged so that either can act raises the hardware ceiling to SIL 3, and the logic solver and the valve must then allow SIL 3 as well.

The buyer's assumptions weigh as heavily in the whole function that the assessor works through in an appendix of its FMEDA report of 2024, with figures that it states are not specific to the product. In the first case the tests find every dangerous failure, the sensor and the final element are tested once a year, and the mission time is five years. The function then averages about 6.8 in 1,000, in the SIL 2 band. The second case takes the assumptions that the report calls realistic: coverage of 90 % for the sensor and 70 % for the final element, a mission time of 25 years and repairs taking 48 hours. The function then averages about 5.8 in 100, in the SIL 1 band. The final element carries most of both totals. With the same parts, the function drops from the SIL 2 band to the SIL 1 band when the assumptions change, and nothing on the switch's certificate changes with them.

What stays with the buyer

The certificate and the manual leave a definite list to the buyer, and each item on it is an assumption that the calculation must state. The list holds the interval and the test to be run, the mission time within the useful life, and the other elements, with certificates and ceilings of their own. A pair of switches for a SIL 3 function adds the β of Chapter 14. The buyer estimates that β for the two switches as installed, since each certificate describes one switch. The rates remain predictions until the site's own records test them (Chapter 20). The safety requirements specification of Chapter 17 carries every one of these assumptions, so that the people who test, bypass and change the function in service know what the calculation took for granted.

Read the certificate and the manual into the calculation

Before choosing a part, check that its certificate and manual cover the model, output, mode, option code and firmware to be installed, and ask the assessor which revision is in force. Carry the manual's conditions into the safety requirements specification of Chapter 17: the diagnostic interval against the process safety time, the useful life as the longest mission time, and the coverage of the test the site will actually run. Compute the function's PFDavg from sensor to final element with the site's own interval, and check the target against every element's ceiling. Write the interval and the mission time down as assumptions, so that field records can test them. For a device such as the incubator, treat each part maker's figure the same way, as a statement about the part under its maker's conditions.

+ What this chapter established
  • A certificate states what an element may be used for and on what conditions: the Rosemount 2130's "SIL 3 Capable" is its systematic ceiling, and "SIL 2 @ HFT=0, SIL 3 @ HFT=1" gives its hardware ceilings alone and with a second switch arranged so that either can act.
  • The safety manual completes the certificate with the diagnostic interval, the proof-test coverage by output, mode and test, a useful life of 10 years and the procedures, and it leaves the proof-test interval to the buyer's calculation.
  • With a yearly comprehensive test and a 10-year mission time, the switch's 25 FIT of dangerous undetected failures and its detected failures together average about 1.8 in 10,000. With the switch in PSLG's loop, whose figures for the logic solver and the valve are fictitious, the loop averages about 9.2 in 10,000.
  • A function may claim no more than the lowest of its elements' ceilings and the band of its own average, so that loop, with a single switch, is a SIL 2 function at most although its average lies in the SIL 3 band.