§ Lessons

Lessons.

The chapters yield ten working rules, at least one from each part and in part order. Each is an action, then the mechanism behind it and its chapters.

  1. Keep the protection apart from the control it guards, and make its likely failures leave the equipment in its safe state. A protection sharing the control's parts can fail with it. De-energizing to trip turns a lost supply or broken wire into a trip (Chapters 1, 2 and 4).
  2. Fit the detection, the decision and the action inside the process safety time, set by how fast the process moves toward harm. Where a check keeps a failure from becoming a hazard, its interval and the time to reach the safe state must together fit inside it (Chapters 4 and 12).
  3. Set the integrity level from the case's own analysis, crediting only layers the event cannot defeat. Layers multiply only when nothing that causes the event can fail them too. An alarm and its operator count only as a complete loop apart from that cause, with time to respond (Chapters 6 to 9).
  4. Credit a second channel only after finding what the two share, and a proof test only for the failures it can reveal. A shared design, supply or batch of parts can fail both at once. Failures outside a test's coverage accumulate however often it runs (Chapters 11, 13 and 14).
  5. Guard against systematic failure in how each part is specified, designed, coded and checked, since no rate describes it. A design fault sits in every copy and acts whenever its conditions occur. A record of use without failure supports a claim only for the conditions it contained (Chapters 15 and 16).
  6. Trace each requirement from hazard to test, and assess the specification before anything is built on it. A wrong limit in the specification passes every check against it, validation included. A change in service that affects what the function must do sends the work back to the requirements (Chapters 17, 19 and 20).
  7. Remove any test position that disables the function, give every bypass a reason, an owner and an end, and repair a protection known to have failed or credit it with nothing. While a protection is disabled or has failed dangerously, it fails every demand (Chapters 7, 11 and 20).
  8. Show that the equipment stays safe with any one fault present. A second means behind the control does nothing in normal use, so its failure gives no sign. A first fault is acceptable only if it will be detected in service or the second means is negligibly likely to fail (Chapter 25).
  9. Read every certificate for its conditions before building its element into a function. The builder takes on the conditions of the element's safety manual, and a function may claim no more than the lowest of its elements' ceilings and the band of its own average (Chapters 21 and 27).
  10. For each market, find the law that places the duty and what links a standard to it, and date both. Law and standard are written by different bodies and change on different dates, and the link between them differs from one market to the next (Chapters 28 to 30).