+ Part VIII · Quality and regulation, as of November 2026
How the law reaches the standards.
In June 2023 the EU adopted a Regulation on machinery to replace its Machinery Directive, and the Regulation applies from 20 January 2027. Laws of this kind decide who must carry out the method of the earlier parts, and how a regulator checks that it was carried out, and they change on dates that can be stated. Part VIII maps the method onto the law in force as of November 2026, each status as its source dates it. Chapter 28 follows European and UK law from the rules for machines to the duties of major hazard sites. Chapter 29 asks how US agencies tie the standards to their rules for plants, devices, vehicles and aircraft, and Chapter 30 how India's regulators do so, and what changed there after the Jaipur depot fire of 2009.
From directives to duties.
+ The questionHow does European and UK law reach the standards, from machines to major hazard sites?
Standards that are not the law
After Buncefield, Britain's regulators, industry bodies and the Trades Union Congress agreed new standards for the large petrol tanks of major hazard sites. The standards cover each vertical tank above ground that stores petrol, has walls more than 5 m high and is filled at more than 100 m³ an hour. For each such tank they set the overfill protection that Chapter 22 follows barrier by barrier, with SIL 1 as its minimum. The Process Safety Leadership Group, or PSLG, in which those bodies were represented, published the standards in its final report of December 2009.
The standards are guidance, not law. An operator that follows them will normally be doing enough to comply with the law, and an operator may use other measures instead. The guidance is "not an authoritative interpretation of the law", as the report itself states. The law in question is the operator's general duty under COMAH, which the fourth section sets out. That duty also asks that the risk be reduced as low as reasonably practicable (Chapter 6). For one kind of tank, the guidance gives the operator a definite means of meeting the duty. Where meeting the guidance in full may not be reasonably practicable for an existing site, the final decision on the degree of compliance is a matter between the operator and the Competent Authority, not one the guidance settles.
The duty, the guidance and the link between them are three parts that recur wherever European and UK law reaches a standard. A law places a duty on a named party, the maker who places a product on the market or the operator of a site, and says what must be achieved. A standard sets out one technical way to achieve it. A presumption joins the two: the party that follows the standard is taken to meet the duty, and the party that chooses another way must show by its own analysis and tests that it meets the duty. Law and standard are written by different bodies and change on different dates.
The presumption written into EU product law
In EU product law the link is written into the law itself. A harmonized standard is a European standard developed by a recognized European standards organization following a request from the European Commission. Its reference is published in the Official Journal of the European Union, and the Commission keeps the references in lists by legislation, one of them for machinery. The Machinery Regulation states the link for machines, and its Annex III sets out their essential health and safety requirements. From 20 January 2027, a machine that conforms to harmonized standards whose references are published in the Official Journal is presumed to conform to those requirements, as far as the standards cover them. That is the presumption of conformity.
Makers need not use harmonized standards and are free to choose another technical solution, as the Commission states. The presumption has two limits. First, it covers only the requirements that the standard addresses, so a maker that follows one standard must still show conformity with every requirement the standard leaves open. Second, it attaches only to a published reference, since the Commission treats publication of the reference as a precondition for the presumption. The machinery standards of Chapter 23 therefore give it only where their references are published.
The Machinery Regulation from 20 January 2027
The Machinery Regulation, Regulation (EU) 2023/1230, was adopted on 14 June 2023, published on 29 June and entered into force on 19 July 2023. It applies from 20 January 2027, and with effect from the same day it repeals the Machinery Directive, 2006/42/EC, the Directive that Chapter 19 names. The text first published gave 14 January 2027 for both; a corrigendum of 4 July 2023 corrected the dates to 20 January. Machinery placed on the market before 20 January 2027 must comply with the Directive and may stay available afterward, and EC type-examination certificates issued under the Directive remain valid until they expire.
Two provisions of the Regulation bear on functional safety. The first defines a safety component as "a physical or digital component, including software", designed to fulfill a safety function and placed on the market on its own, so software that performs a safety function and is sold separately is a safety component in its own right. The second is the Regulation's Annex I, which lists high-risk categories of machinery. Its Part A includes safety components that ensure safety functions with fully or partially self-evolving behavior, using machine-learning approaches, and machinery with embedded systems that behave that way.
Chapter 15's systematic capability is earned by how a fixed design was specified, built and checked. A component that changes its own behavior after it is placed on the market no longer matches the design that was checked. For such components conformity assessment "should be carried out by a third party", in the words of the Regulation's recitals.
Who assesses a machine therefore follows from its place in Annex I. Internal production control is the route in which the maker assesses its own product. Machinery in Part A may not use it and must take one of the third-party routes, which the Regulation lists as module B with C, module H or module G. Machinery in Part B may use internal production control if it is built in accordance with the harmonized standards, and otherwise takes one of the same third-party routes. Machinery outside Annex I uses internal production control. For Part B, the harmonized standard decides whether the maker may assess its own conformity at all.
A maker builds two versions of one machine. The case is hypothetical: it assumes that no category of Annex I names the machine's type. In the first the safety functions run on fixed logic; in the second an embedded system that ensures a safety function adjusts its own behavior by machine learning, and that system is not sold on its own. Placed on the market on 19 January 2027, either version must comply with the Directive and may stay available afterward. Placed on the market a day later, both come under the Regulation. The second is then machinery of Annex I Part A, point 6, so a third party must assess it in respect of that embedded system only. The first lies outside Annex I, so its maker assesses it alone, by internal production control. The date decides which law applies, and under the Regulation the self-evolving embedded system brings a third party into the assessment of that system.
Duties that stay with a site
Product law acts when a product is placed on the market, and it binds the maker. Major-hazard law binds the operator of a site for as long as the site holds dangerous substances. Its European form is Seveso III, Directive 2012/18/EU on the control of major-accident hazards involving dangerous substances. The Directive dates from 4 July 2012 and is in force in November 2026. It places a general obligation on every operator to take all necessary measures to prevent major accidents and to limit their consequences, and it requires a major-accident prevention policy in writing. Establishments that hold the larger quantities form the Directive's upper tier, and they also prepare a safety report and an internal emergency plan.
Seveso III also sets a timetable for checking the duties. It asks for site visits at intervals that do not exceed one year for upper-tier establishments and three years for lower-tier ones, unless the inspection program is based on a systematic appraisal.
In Great Britain the Control of Major Accident Hazards Regulations 2015, or COMAH, implement all but three of the Directive's articles and are in force in November 2026 (Chapter 6). Northern Ireland has its own Regulations of the same year. The operator of a fuel depot under COMAH holds its duties for as long as the depot runs, and Chapter 17 shows that Buncefield's operator could not hand them to the firm whose staff ran the site. The SIL 1 minimum of Chapter 22 reaches the depot through the general duty, by way of the guidance that the first section described. PSLG wrote that guidance under the COMAH Regulations of 1999, and the 2015 Regulations keep the duty and implement Seveso III's general obligation.
Site law also acts after an accident. For Buncefield, HSE and the Environment Agency secured convictions against five companies, which were ordered to pay almost £10 million in fines and costs.
Great Britain after EU exit, and medical devices
The UK implemented the Machinery Directive as the Supply of Machinery (Safety) Regulations 2008. Amendments made for EU exit in 2019 apply them to Great Britain alone, and as of November 2026 the 2008 Regulations remain its machinery law. The Regulations set the requirements a machine must meet before it is placed on the GB market or put into service, and HSE enforces them for machinery at work. Under them, the presumption of conformity rests on designated standards, technical specifications adopted by a recognized standards body or designated by the Secretary of State and used to achieve that presumption.
The marking differs by market as well. Since 1 October 2024 Great Britain has recognized the CE marking for machinery indefinitely, beside its own UKCA marking. Machinery for the EEA market still needs the CE marking, and so does machinery for Northern Ireland, which follows separate guidance under the Windsor Framework.
Medical devices reach the European market under laws of their own, and the incubator of Chapter 4 is a medical device. Its maker affixes the CE marking, followed by a notified body's identification number where applicable. By that marking a manufacturer indicates that a device conforms to the applicable requirements of the Medical Device Regulation. Under the Regulation's classification rules, an active therapeutic device that administers energy to the body or exchanges energy with it is class IIa, or class IIb where it may do so in a potentially hazardous way, and the Medical Device Coordination Group's classification guidance names incubators for babies among its class IIb examples. The device guides follow that route in their dated parts: Every drop accounted for takes an infusion pump through the same Regulation in its Chapter 29, and Where the heat goes shows in its Chapter 27 how that Regulation classifies an energy device.
In the technical file of a machine or a safety component, state the law it is placed under and the date that decides it. List the harmonized standards it follows, checked against the list the Commission keeps under that law, and for every requirement no listed standard covers, record the analysis and tests that show conformity. For a component whose behavior evolves by machine learning, plan for a third-party assessment. For a petrol tank in PSLG's scope on a COMAH site, set its overfill function against PSLG's guidance, and record every departure with the reasoning that will be shown to the Competent Authority. For a machine sold in both the EU and Great Britain, check each market's law and marking on its own.
- After Buncefield, regulators and industry set standards for large petrol tanks as guidance: an operator that follows it will normally meet the law, and at an existing site any shortfall is settled between the operator and the Competent Authority.
- In EU product law a harmonized standard is voluntary, and one whose reference is published in the Official Journal gives a presumption of conformity with the essential requirements it covers.
- The Machinery Regulation applies from 20 January 2027, when the Machinery Directive is repealed; it counts software placed on the market on its own for a safety function as a safety component, and for Annex I Part B the harmonized standards decide whether the maker may assess its own conformity.
- Seveso III and COMAH 2015 bind a major hazard site's operator for as long as the site holds dangerous substances. As of November 2026 Great Britain's machinery law is still the Supply of Machinery (Safety) Regulations 2008, which implemented the Machinery Directive.