23 — Machines

Guards, stops and robot cells.

+ The questionHow do ISO 13849-1 and IEC 62061 apply the method to a guard, a stop and a robot cell?

A protective function called on all day

A light curtain across the front of a press stops the stroke when a hand breaks one of its beams. An emitter on one side of the opening sends a row of beams across it to a receiver. While every beam arrives, the receiver's outputs let the press run, and when any beam is interrupted the outputs switch off and the ram is halted. In Chapter 4's terms the curtain is the function's sensor, the parts that halt the ram are its final element, and the safe state is a ram at rest. The curtain is therefore a guard that blocks nothing: it lets the hand in and stops the hazard instead.

The incubator's cutout is called on when its control loop fails, no more than once a year (Chapter 8). The curtain's demand is a hand in the beams while the ram could descend, and it comes with every part that an operator loads by hand, many times a shift. Such a function is in Chapter 8's high-demand mode. A dangerous failure of the curtain does not wait long for a demand to reveal it, because the next reach meets it, so how rarely the function may fail is counted per hour of running, not per demand.

Two standards set the method for such functions. ISO 13849-1:2023 covers the safety-related parts of a machine's control system in the high-demand and continuous modes, as Chapter 8 set out, and sets neither the safety functions nor the levels of a particular application. It is the fourth edition, published in April 2023. IEC 62061:2021 + AMD1:2024 + AMD2:2026 is IEC's machinery standard within the framework of IEC 61508. It covers safety-related control systems in the same modes, on machines that are not hand-portable. Under EU law either standard gives a maker a presumption of conformity only where its reference is published (Chapter 28).

A robot cell has a standard of its own. ISO 10218-2:2025 sets requirements for integrating industrial robot applications and robot cells, through their design, commissioning, operation and maintenance to their disposal. It is the standard's second edition, published in February 2025. IEC 60204-1, the standard for the electrical equipment of machines, sorts the ways a machine is stopped into three stop categories, and a robot maker's manual defines them. A Category 0 stop halts the robot by removing power at once, a Category 1 stop brings it to a controlled halt and then removes power, and a Category 2 stop halts it with power left on the drives. In a 2021 trade-press article Klancewicz, of Omron Automation Americas, a maker of automation equipment, gives the rule for an emergency stop: it must act as a Category 0 or a Category 1 stop, chosen by a risk assessment.

Three questions set the required level

The level a function needs comes from the hazard it guards, through three questions in ISO 13849-1's own risk graph, each answered with one of two classes. S is the severity of the injury, slight or serious, and F is the exposure to the hazard, rare or frequent, as IDEC, a maker of safety components, summarizes the two. P is the possibility of avoiding the harm, possible under specific conditions or scarcely possible, as Pilz, a maker of safety relays and controllers, words the classes for the 2023 edition. The answers lead along one path to the required performance level, or PLr, of the function. The graph keeps three of Chapter 8's four questions, the consequence, the exposure and the avoidance, and has no W, the probability of the unwanted occurrence.

For the press each answer is the worse class. A ram closing on a hand causes an injury that is normally irreversible, so the severity is S2. An operator who loads every part by hand is exposed frequently, so the exposure is F2. The stroke is over before a hand in the die can be withdrawn, so avoidance is scarcely possible, P2. In each question the higher class is the worse, as in Chapter 8's graph, so a path that takes the worse class three times ends at the top of the scale, PL e. The interlock on the door of a robot cell, which stops the robot when the door opens, is graded by the same questions. There the answer to F depends on how often people enter the cell, so the door may need a different level from the curtain.

Since the 2023 edition, P has been chosen by a new method in Annex A, and the classes are still defined in words. Chapter 8's caution applies to them: a class chosen from its definition alone can move the level by a step without anyone seeing it. A team that called a crushed finger a slight injury, or the exposure rare because each reach is brief, would grade the press below PL e and design a curtain to match.

Each level is a band of dangerous failures per hour

A performance level, or PL, is a band of Chapter 8's PFH, the frequency of dangerous failure per hour. PL a lies between 1 dangerous failure in 100,000 hours and 1 in 10,000. PL b asks for fewer than 1 in 100,000, PL c fewer than 3 in a million, PL d fewer than 1 in a million and PL e fewer than 1 in 10 million, as Pilz gives the limits. PL b and PL c split one tenfold step at 3 in a million, so the five levels cover four tenfold steps, down to PL e's floor of 1 in 100 million hours.

The parts' reliability enters as the MTTFD of each channel, its mean time to dangerous failure: Chapter 10's MTTF counted over dangerous failures only and stated in years. With a constant rate, the MTTFD is the reciprocal of the dangerous failure rate. It falls into three bands, low from 3 to below 10 years, medium from 10 to below 30 and high from 30 to 100, and a channel below 3 years does not qualify. These are the bands of the 2006 edition, as Keyence, also a maker of safety components, gives them. The high band ends at 100 years, which IDEC gives as the ceiling on what a channel may claim, with one exception, set out in the next section.

49 — Performance levels as bands of dangerous failures per hour
PERFORMANCE LEVEL ISO 13849-1 SIL IEC 62061 PL a PL b PL c PL d PL e SIL 1 SIL 2 SIL 3 NO SIL 1 IN 10,000 HOURS 1 IN 100,000 1 IN A MILLION 1 IN 10 MILLION 1 IN 100 MILLION 3 IN A MILLION DANGEROUS FAILURES PER HOUR (PFH) ONE CHANNEL, MTTFD 30 YEARS: 3.8 IN A MILLION ONE CHANNEL, MTTFD 100 YEARS: 1.1 IN A MILLION the most an unchecked channel may claim: PL c, short of PL d PL bands as Pilz's overview of ISO 13849-1 gives them; SIL beside PL as DGUV Test Information 08 (2026) pairs them. Marker rates computed from the MTTFD for one channel without diagnostics.
Safety functionFocal detail
Plate 49 — Each performance level is a band of dangerous failures per hour, PL b and PL c sharing one tenfold step, and IEC 62061's SIL 1 to SIL 3 meet them at the same rates. One channel without checks, credited with at most 100 years, fails dangerously about 1.1 times in a million hours, inside PL c.
Solved example: how far one unchecked channel reaches

The function here has one channel and no checks. Every dangerous failure of one of its parts is then a failure of the function, so the function's PFH is the channel's dangerous failure rate. At the 100-year ceiling, with 8,760 hours in a year, the channel runs 100 × 8,760 = 876,000 hours for each dangerous failure, about 1.1 in a million per hour. That rate lies between 1 and 3 in a million, in PL c's band. At 30 years, the bottom of the high band, the channel runs 30 × 8,760 = 262,800 hours for each dangerous failure, about 3.8 in a million per hour, in PL b's band. PL d asks for fewer than 1 in a million, so one unchecked channel cannot reach it, whatever its parts, and against the press's PL e it fails dangerously more than 10 times too often. The result holds for one channel without diagnostics.

Categories add checks and a second channel

A function's structure falls into one of ISO 13849-1's five categories, B, 1, 2, 3 and 4, and the upper three add what one unchecked channel lacks. Category B is a basic single channel, and Category 1 is the same channel built from well-tried components. Category 2 adds diagnostics to the single channel: a test that checks it. Category 3 adds a redundant channel with diagnostics, and Category 4 asks that the diagnostics of the redundant channels detect at least 99 % of dangerous failures. The checks are those of Chapter 12, and the second channel is the redundancy of Chapter 13, here under the standard's own names.

Each category also bounds what its channels may claim. A Category B channel is credited with an MTTFD of 3 to below 30 years, and a Category 1 channel with 30 to 100. Categories 2 and 3 allow 3 to 100 years and ask for a diagnostic coverage of at least 60 %. Category 4 asks for at least 99 % and allows 30 to 2,500 years per channel, the one case in which a channel may claim more than 100 years. These are the 2023 edition's ranges, as DGUV, the German statutory accident insurance, tabulates them in a 2026 publication.

50 — ISO 13849-1's five categories
CATEGORY B SENSOR LOGIC SOLVER FINAL ELEMENT BASIC CATEGORY 1 SENSOR LOGIC SOLVER FINAL ELEMENT WELL-TRIED COMPONENTS CATEGORY 2 SENSOR LOGIC SOLVER FINAL ELEMENT TEST CATEGORY 3 SENSOR LOGIC SOLVER FINAL ELEMENT SENSOR LOGIC SOLVER FINAL ELEMENT CROSS-CHECK CATEGORY 4 SENSOR LOGIC SOLVER FINAL ELEMENT SENSOR LOGIC SOLVER FINAL ELEMENT CROSS-CHECK CHANNELS 1 1 1 2 2 MTTFD PER CHANNEL 3 TO BELOW 30 YEARS 30 TO 100 YEARS 3 TO 100 YEARS 3 TO 100 YEARS 30 TO 2,500 YEARS DIAGNOSTIC COVERAGE NO CHECKS NO CHECKS AT LEAST 60 % AT LEAST 60 % AT LEAST 99 % the only category that credits a channel with more than 100 years Schematic. Categories as Doug Nix's 2023 summary of ISO 13849-1:2023 gives them; MTTFD ranges and coverage minimums of the 2023 edition as DGUV Test Information 08 (2026) tabulates them.
DiagnosticsSafety functionFocal detail
Plate 50 — Category B is a basic single channel and Category 1 the same built of well-tried components; Category 2 adds a test, and Categories 3 and 4 a redundant channel with checks. Each category bounds the MTTFD its channels may claim, and only Category 4, which asks for at least 99 % coverage, credits more than 100 years.

The coverage enters as DCavg, Chapter 12's diagnostic coverage averaged over the function. It is graded none below 60 %, low from 60 % to below 90 %, medium from 90 % to below 99 % and high at 99 % or more, in the 2006 edition's bands as Keyence gives them. Coverage counts because a dangerous failure that the checks detect does not wait for the next hand. When the checks find the failure, the function stops the press, the first of Chapter 12's two reactions, and the failure becomes a stop instead of an injury.

For the press's curtain, a second channel and its checks change the solved example's result. With two channels that can each halt the ram, one dangerous failure leaves the function working. A cross-check of the two channels' outputs finds that failure, and the press stays stopped until the fault is repaired (Chapter 12). The function then fails dangerously only when a failure escapes the checks and the second channel fails too, or when one cause defeats both channels. Its rate therefore falls far below either channel's (Chapter 13).

Two channels earn that credit only while no shared cause can defeat both. The defenses against a shared cause are scored on ISO 13849-1's own checklist, in its Annex F, and a design must earn at least 65 of the 100 points, as Keyence and IDEC both state the rule. This checklist sets a pass mark, where Chapter 14's checklist from IEC 61508 turns a score into a β factor. The DGUV publication adds that ISO 13849-1's simplified method fixes β at no more than 2 %.

A category names a structure, and the level needs its numbers too

A category is easily taken for a level, as if Category 3 meant one PL. The category fixes the structure: the channels, the checks and the ranges its numbers may take. The level follows from the category together with the MTTFD, the DCavg and the common-cause score. Two Category 1 functions, one with its channel at 30 years and one at 100, fall in PL b and in PL c, as the solved example shows.

IEC 62061 states the same targets as SILs

Under IEC 62061 the same function is graded by Chapter 8's SIL for high demand, and the two scales meet at the PFH. Below 1 dangerous failure in 100,000 hours, SIL 1 spans PL b and PL c. Below 1 in a million, SIL 2 matches PL d, and below 1 in 10 million, SIL 3 matches PL e. PL a lies between 1 in 100,000 and 1 in 10,000 hours and has no SIL. The pairing matters to a builder who combines certified subsystems from different sectors, and such combinations are the subject of the DGUV publication that sets the pairing out.

The two standards come from two bodies. ISO's committee TC 199 wrote ISO 13849-1, and IEC's committee TC 44 wrote IEC 62061, which IEC places within the framework of IEC 61508. The standards share the modes and the measure and differ in vocabulary and in some numbers. β runs from 1 % to 10 % under IEC 62061, against no more than 2 % in ISO 13849-1's simplified method, by DGUV's account. The electrical hazards of the control equipment itself fall outside IEC 62061.

One part can carry both ratings. TÜV SÜD certifies Pilz's PSS 4000 automation system to the European editions of IEC 62061:2021, of ISO 13849-1:2015 up to Category 4 and PL e, and of IEC 61508 up to SIL 3. A part rated on one scale therefore enters a function designed to the other through its frequency of dangerous failure, not the name of its level, since a SIL 1 part may sit in PL b's band or in PL c's.

Validation moves into Part 1

The numbers so far cover random failures. Chapter 3's systematic failures are met by how a function is specified, built and checked, and ISO 13849-1 now sets more of that work itself. Since the 2023 edition, clause 7 sets software safety requirements, Annex M gives additional information for the safety requirements specification of Chapter 17, and Annex N lists fault-avoiding measures for software. Validation is Chapter 19's check that the finished function meets its specification, and it has moved into clause 10 of Part 1.

According to a 2023 summary of the edition's changes by Doug Nix, a consultant, clause 10 takes in the normative text of ISO 13849-2:2012, the part titled Validation, and updates it. ISO 13849-2 was last reviewed and confirmed in 2018 and stands at ISO's stage "to be revised". For the press, validation is where the curtain as built is shown to meet the PLr that the three questions set.

ISO 13849-1 also draws the V itself, for the software of a safety function. The 2015 edition sets out the software safety lifecycle as a V in its Figure 6, and the 2023 edition applies the V-model of that lifecycle in its informative Annex J. Down the left arm of the 2015 figure run the safety requirements specification, the system design, the design of each module and the code. Each level of design becomes the specification that the level below works from. Up the right arm run the module tests, the integration tests and, at the top, validation, which the 2023 edition places in clause 10.

The arms are linked by reviews and tests. For embedded software, the code is reviewed against its module design, and each module test shows that every requirement of that design has been implemented, as Bömer and colleagues at IFA, DGUV's research institute, read the 2015 edition in a 2021 guidance report. The target enters at the top of the left arm as the PLr that the risk graph set.

51 — ISO 13849-1's V for safety-related software
SAFETY REQUIREMENTS SPECIFICATION SYSTEM DESIGN MODULE DESIGN CODE MODULE TEST INTEGRATION TEST VALIDATION EVERY REQUIREMENT OF THE DESIGN SHOWN IMPLEMENTED CODE REVIEWED AGAINST ITS MODULE DESIGN EMBEDDED SOFTWARE EACH LEVEL'S OUTPUT IS THE SPECIFICATION FOR THE NEXT CLAUSE 7 · SOFTWARE SAFETY REQUIREMENTS CLAUSE 10 · SINCE 2023, TAKEN IN FROM ISO 13849-2:2012 PLr FROM S, F, P validation now in Part 1, at the top of the V Schematic, after ISO 13849-1:2015 Figure 6 and the clauses of ISO 13849-1:2023, on the guide's V of Chapter 19.
DiagnosticsSafety functionFocal detail
Plate 51 — ISO 13849-1 draws the software of a safety function as a V: the specification, the system design, the module design and the code down the left arm, and the module tests, the integration tests and validation up the right, linked by reviews and tests. The target enters at the top as the PLr that the risk graph set, and since 2023 the validation at the V's top sits in clause 10 of Part 1.
What ISO 13849-1 and IEC 62061 add
  • A risk graph that sets the PLr from severity, exposure and the possibility of avoidance alone, without the probability of the unwanted occurrence that Chapter 8's graph asks for.
  • A β factor fixed at no more than 2 % in ISO 13849-1's simplified method, where IEC 62061 allows 1 % to 10 %, by DGUV's account.
  • Software safety requirements in clause 7 and fault-avoiding measures for software in Annex N, both since the 2023 edition.
  • A software safety lifecycle drawn as a V in Figure 6 of the 2015 edition, which the 2023 edition applies in its informative Annex J.
Grade each machine function from its own hazard

Set the PLr of each function from S, F and P, and write down why each class was chosen, taking the press's curtain and a robot cell's door separately. Convert each channel's MTTFD to a dangerous failure rate per hour and place it in the bands before choosing a category: one channel without checks stops at PL c. Claim no MTTFD beyond the range of the category, and score the common-cause checklist before crediting a second channel. Record the edition behind every band. Where a subsystem rated by SIL joins one rated by PL, match them by their PFH.

+ What this chapter established
  • A press's light curtain is called on many times a shift, so its failures are counted per hour. ISO 13849-1:2023 grades such functions as performance levels, PL a to PL e, bands of dangerous failures per hour, and its risk graph sets the level a function needs from severity, exposure and the possibility of avoidance.
  • With a constant rate, a channel's MTTFD is the reciprocal of its dangerous failure rate. Outside Category 4 it is credited at no more than 100 years, so one channel without checks reaches PL c at best.
  • The five categories run from a basic single channel to redundant channels with diagnostics, each with its own MTTFD range and, from Category 2, a minimum diagnostic coverage. Common cause is scored on a checklist with a pass mark of 65 of 100 points.
  • IEC 62061 states the same targets as SIL 1 to SIL 3, which meet the performance levels at their PFH, and the 2023 edition of ISO 13849-1 takes validation into its clause 10.